Automatic gas burner control unit for gas, gas/oil and oil burners in continuous operation. Monitoring is by means of UV sensor QRA 5.. (gas and oil burners) or by means of an ionization sensor electrode (gas and blue flame burners). Also for quick steam generators. Also for WLE according to DIN 4794. 110 volt version available on request.
Technical data:
Pre-aeration time (t1): 37s
1st safety time (TSA): 2.5s
2nd safety time (t9): 5s
Mains voltage: AC220 V -15%...240 V +10%
Mains frequency: 50 ... 60 Hz ±6%
Power consumption: 3.5 VA
Temperature range: -20 ... +60°C
Air humidity: < 95% r.h.
Protection class: IP40
Dimensions: approx. 103 x 103 x 123 (L x W x H in mm)
Weight: approx. 1.12 kg
Technical data:
Pre-aeration time (t1): 37s
1st safety time (TSA): 2.5s
2nd safety time (t9): 5s
Mains voltage: AC220 V -15%...240 V +10%
Mains frequency: 50 ... 60 Hz ±6%
Power consumption: 3.5 VA
Temperature range: -20 ... +60°C
Air humidity: < 95% r.h.
Protection class: IP40
Dimensions: approx. 103 x 103 x 123 (L x W x H in mm)
Weight: approx. 1.12 kg