The QGO20 is an oxygen sensor designed for acquiring the residual oxygen content of flue gases in heat generation plant burning natural gas or light fuel oil. Together with the control unit, the QGO20 monitors and controls the combustion process. In conjunction with the LMV52 automatic burner control units for residual oxygen control, combustion efficiency is improved and pollutant emissions are minimized. Can be used for flue gas temperatures of max. 300 °C at the measuring point.
Version: 230V AC, 50-60 Hz
Power consumption: Max. 90 W, typically 35 W (regulated)
Protection class: IP40, ensure by installation
Permitted fuels: Light oil (EL), natural gas (H)
Measuring range: 0.2...20.9% O2
Required operating temperature of the measuring cell: 700 °C ±50 °C
Important note: This probe is a wearing part. For this reason, contrary to our terms of delivery and payment, the warranty period is only 9 months.
Version: 230V AC, 50-60 Hz
Power consumption: Max. 90 W, typically 35 W (regulated)
Protection class: IP40, ensure by installation
Permitted fuels: Light oil (EL), natural gas (H)
Measuring range: 0.2...20.9% O2
Required operating temperature of the measuring cell: 700 °C ±50 °C
Important note: This probe is a wearing part. For this reason, contrary to our terms of delivery and payment, the warranty period is only 9 months.