Honeywell BCU 460W3P2 Burner control unit

Typ 460W3P2C0D0000K2E0-/LM400WF0O0E1-

Product number: 1073550
plus Vat

(sale to commercial customers only)

Manufacturer #: 88680866
Weight: 6.24 kg
Datasheet: after login only!
Stock status:   please ask
  
Item number: 1073550
Your net price: 1.542,66 €
Honeywell burner control unit BCU 460W3P2C0D0000K2E0-/LM400WF0O0E1-
Successor model for 84630060 with P00006. Attention: Rewiring according to wiring diagram required!

On-site housing for controlling, igniting and monitoring pulse-controlled, modulating or step-controlled gas burners. For continuous operation with ionization monitoring or UV monitoring with UV probe UVD. Intermittent operation with UV sensor UVS. Display of program status, device parameters and flame signal. Manual operating mode. Diagnosis and setting of device parameters via optical interface and BCSoft PC software. EU-certified, FM and EAC approved, certified for systems up to SIL 3 (corresponds to PL e).

Series: Standard version
Mains voltage: 230 V~, 50/60 Hz
Ignition transformer: 8 kV, 12 mA, ED 100 %
Flange plate: M32
Valve monitoring system: None
High temperature operation: None
Input function: None
Pressure monitoring: None
Connector plug: With spring terminals
Packaging: Individual packaging
Energy supply: Via safety chain
Power module: Power module
Series: 400
Mains voltage: 230 V~, 50/60 Hz
Air drive: None
Optional output: None
Power supply: Via L1

I004 Flame monitoring: Ionization
I050 Function contact 80, 81/82: Fault message
I052 Function contact 95/96: Burner 1 operating signal
I053 Function contact 95/97: Burner 1 operating signal
I061 Function terminal 1: Start 1
I062 Function terminal 2: Reset
I068 Function terminal 35: Safety chain
A001 Burner 1 switch-off threshold: 2 micro A
A003 External light test: In standby
A007 Start-up test burner 1: 1
A093 Pre-ignition time tVZ: 0 s
A094 1st safety time start-up: 5 s
A095 Flame stabilization time 1 tFS1: 0 s
A078 Burner application: Burner 1
A076 Function V5: Off
A009 Restart: Burner 1
A074 Combustion operating mode: Flame mode
A043 Run-on: Off
A039 Run-on time: 0 s
A019 Safety time operation: 1 s
A061 Minimum operating time tB: 0 s
A062 Minimum pause time tMP: 0 s
A067 Operating time in manual mode: Limited to 5 min
A087 Flushing (bus): Off
A080 Fieldbus communication: Off
A081 Kromschröder Safety Link: Off