FEMA Honeywell Pressure switch DWR06

0.1 - 0.6 bar, G 1/2", max. pressure 6 bar

Product number: 1104235
plus Vat

(sale to commercial customers only)

Manufacturer #: DWR06
Weight: 0.62 kg
Datasheet: after login only!
Stock status:   on request
  
Item number: 1104235
Your net price: 344,50 €
DWR 06 Fema-Honeywell pressure switch, special design for pressure monitoring of hot water, fuel gases and liquid fuels. Replaces DNA 6.

Technical Data:
Fixed switching differential
Adjustable pressure range: 0.1...0.6 bar
Fixed hysteresis: 0.04 bar
Max. pressure: 6 bar
Max. Gas pressure: 6 bar
Pressure type: Overpressure, relative
Pressure connection: Female thread G¼”, male thread G½”
Electrical connection: Plug according to plug DIN EN 175301
Protection class: IP 54
Material of the switch housing: Robust housing made of seawater-resistant die-cast aluminum GDAlSi12
Materials in contact with the medium: 1.4104 + 1.4571
Medium temperature: -25...70°C
Max. Medium temperature: Short-term temperatures of up to 85 °C are permissible. Higher medium temperatures are possible if suitable measures (e.g. siphon) to ensure the above limit values on the switching device (see accessories for pressure switches / transmitters).
Note on ambient temperature:
At ambient temperatures below 0 °C, make sure that no condensation is generated in the sensor and in the switching device.
Switching function: 8 A at 250 V AC, 5 A at 250 V AC inductive, 8 A at 24 V DC, 0.3 A at 250 V DC

Registrations: ID 0000007042 according to VdTÜV bulletin 100, edition 07.2006 and DIN EN 12952-11 and DIN EN TV.DWFS (SDBFS). 12-281 according to VdTUEV bulletin 100, edition 07.2006 and DIN EN 12952-11 and DIN EN 12953-9:2007 ID 0000035004 according to DIN EN 764-7:2002 and DIN EN 13611:2008 CE-0085CL0343 according to DIN EN 1854, edition 07.2006 01 202 931-B-11-0003 according to directive 97/23 EC SIL2 according to IEC 61508-2