Cable temperature sensor KTY 81-210 for temperature measurement in gaseous media in heating, ventilation and air conditioning systems. Also suitable for measuring in liquid media (e.g. piping systems) in conjunction with an immersion sleeve. Designed for connection to controller and display systems.
0°C = 1630 Ohm, 10°C = 1772 Ohm, 20° C = 1922 Ohm.
Total length 3000 mm, installation length 50 mm, connection cable cross-section 0.25mm² / L=3000 mm, ambient temperature silicone cable: -50°C...+150°C, (other cables on request), connection 2-wire (standard), sensor sleeve stainless steel 1.4571, ø=6mm, other sensors and installation lengths on request! Alternative to KVT boiler and cylinder sensor.
0°C = 1630 Ohm, 10°C = 1772 Ohm, 20° C = 1922 Ohm.
Total length 3000 mm, installation length 50 mm, connection cable cross-section 0.25mm² / L=3000 mm, ambient temperature silicone cable: -50°C...+150°C, (other cables on request), connection 2-wire (standard), sensor sleeve stainless steel 1.4571, ø=6mm, other sensors and installation lengths on request! Alternative to KVT boiler and cylinder sensor.