Digital automatic burner control for gas blower and combination burners, remote unlockable, 2-stage, safety time 3 sec., flame monitoring with ionization probe, infrared flicker detector IRD 1020 or UV flame sensor UVD 971. Replacement for MMI 810 Mod.32/33 (rewire air pressure monitor from terminal 5 to terminal 4, interference button extension required as height compensation).